Non-Combustibility Apparatus

Non-Combustibility Apparatus

Product Description

This equipment is used to test the non-combustibility of the main components of homogeneous and non-homogeneous building products under specified conditions. In conjunction with GB/T 8624-2012, it evaluates the combustion performance classification of the tested building materials to determine whether they meet the combustion performance requirements or for quality control purposes.

Applicable Standards

Conforms to the following standards:

GB/T 8624-2012

GB/T 5464-2010

GB 8624-2012

GB/T 40238-2021

ISO 1182:2002

ISO 1182:2020

EN 13238

Operating Environment and Other Requirements

Operating Conditions: Temperature 23 ± 5°C, humidity 50 ± 20%. Room temperature variation during the test should not exceed 5°C. The test setup must not be placed near air vents or exposed to direct sunlight or artificial radiation.

Power Supply: Single-phase AC 220V ±5%, 50 Hz

Balance: Accuracy not less than 0.01 g (provided by the user)

Technical Specifications

Heating Voltage: 0–100 V

Furnace Power: 0–1500 W

Heating Temperature: Ambient temperature to 1000°C

Thermocouple Specifications: Wire diameter 0.3 mm, outer diameter 1.5 mm, Type K, Class 1 precision

Number of Thermocouples: 3 (1 for furnace temperature, 1 for sample surface temperature, 1 for sample center temperature; a second furnace temperature thermocouple is optional)

Temperature Measurement Accuracy: Class 1, ±1.5°C or 0.4%t, whichever is greater

Sample Dimensions: φ45 × 50 mm

Furnace Tube Dimensions: Height 150 mm ±1 mm, inner diameter 75 mm ±1 mm, wall thickness 10 mm ±1 mm

Temperature Control Time: 40–60 minutes (from ambient to stable 750°C)